HCT40 technical data

Measurement

Measuring range
100–5000 mm
Sensor type
Coaxial capacitance
Accuracy class
0.2 or 0.5
Sampling rate
4 readings per second
Display range
−1999 to 9999
Long-term stability
0.5 % FS/year

Electrical

Supply voltage
DC 24 V, AC-DC 110 V, AC-DC 220 V
Power consumption
≤ 3 W
Analogue output
4–20 mA / 0–10 or 20 mA / 0–5 or 1–5 V DC
Relay outputs
2 pairs
Relay rating
5 A at 250 V AC, 5 A at 30 V DC
Relay life
> 100 000 operations
A/D conversion
24-bit

Mechanical

Ambient temperature
−20 to +70 °C
Medium temperature
−20 to +80 °C
Storage temperature
−40 to +100 °C
Relative humidity
0–80 %
Housing material
Plastic or aluminium alloy
Probe material
Stainless steel
Connection
G1/2, M20×1.5 or to order
Ingress protection
IP65

Values are for the standard configuration. Ranges, threads, probe lengths and output types outside this table are available on request — the datasheet revision for a custom build is issued with the quotation.

Request the PDF datasheet →

Level Sensors & Transmitters

HCT40Capacitive Level Controller

2 relays

Coaxial capacitive level controller with two relay outputs, LED display and 24-bit A/D. 100–5000 mm, 4–20 mA / 0–10 V / 1–5 V selectable, stainless probe. The compact option for simple high/low control on viscous media.

Engineering reply · Evaluation samples available · Custom ranges built to order

  • Two relay outputs for simple high/low duty
  • No moving parts, suits coating media
  • Range 100–5000 mm
  • Plastic or aluminium housing
  • Selectable analogue output

How it works

A two-relay version of the capacitive controller for duties that only need high and low: fill-and-drain on a small tank, high-level alarm plus low-level cut-out on a day tank. The measuring element is identical to the HCT100, so the same suitability for viscous and coating media applies, and the plastic or aluminium housing is lighter where the instrument is bracket-mounted rather than panel-mounted.

Typical applications

  • Day tanks and small mixing vessels
  • High-level alarm with low-level pump cut-out
  • Coating and viscous product level

Not certain HCT40 is the right unit?

Send the medium, range, process connection and the signal your control system accepts. We will confirm the model — or tell you which one fits better — before you commit to an order.

Same family

Other level instruments

View the family →