Factory-direct manufacturer · Xiamen, China · Exporting worldwide

Pressure Transmitters & Controllers

PCD2088 Pressure Transmitter Controller

4 relays

Request a quote

PCD2088 technical data

Measurement

Pressure range
−0.1 to 0, and 0 to 60 MPa
Sensor type
Diffusion silicon, ceramic piezoresistive or ceramic capacitive
Accuracy class
0.2 or 0.5
Overload pressure
1.5× full-scale
Sampling rate
4 readings per second
Display range
−1999 to 9999
Long-term stability
0.5 % FS/year
Power supply effect
≤ 0.1 % FS

Electrical

Supply voltage
DC 24 V
Power consumption
≤ 3 W
Analogue output
4–20 mA / 0–10 or 20 mA / 0–5 or 1–5 V DC
Relay outputs
4 pairs
Relay rating
3 A at 250 V AC, 3 A at 30 V DC
Relay life
> 100 000 operations
A/D conversion
24-bit

Mechanical

Ambient temperature
−20 to +70 °C
Medium temperature
−20 to +80 °C
Storage temperature
−40 to +100 °C
Relative humidity
0–80 %
Housing material
Stainless steel + aluminium alloy
Connection
G1/2, M20×1.5 or to order
Ingress protection
IP65

Values are for the standard configuration. Ranges, threads, probe lengths and output types outside this table are available on request — the datasheet revision for a custom build is issued with the quotation.

Request the PDF datasheet →

Pressure Transmitters & Controllers

PCD2088Pressure Transmitter Controller

4 relays

Pressure transmitter with a 24-bit A/D, LED display, four relay outputs and selectable analogue output. −0.1 to 60 MPa, 0.2 accuracy class, diffusion-silicon, ceramic piezoresistive or ceramic capacitive sensor, stainless and aluminium housing.

Engineering reply · Evaluation samples available · Custom ranges built to order

  • Four relay outputs with keypad-set trip points
  • Selectable 4–20 mA, 0–10/20 mA, 0–5 or 1–5 V output
  • 24-bit A/D, 4 readings per second
  • −0.1 to 60 MPa range
  • Choice of diffusion-silicon or ceramic sensor

How it works

The PCD2088 pairs a pressure sensor with a controller in one 2088 head: 24-bit conversion, a display readable across a plant room, four relays with keypad-set trip points, and a selectable analogue output to the control system. It is the right instrument when a pressure switch and a transmitter are both currently installed on the same line — one device then covers measurement, local indication and interlock, and there is only one calibration record to keep. Sensor type is selected to suit the medium: diffusion silicon for clean gas and liquid, ceramic piezoresistive or capacitive for chemically aggressive service.

Typical applications

  • Replacing separate pressure switch and transmitter
  • Pump and compressor pressure interlock
  • Hydraulic power-unit monitoring
  • Pressure control on gas trains

Not certain PCD2088 is the right unit?

Send the medium, range, process connection and the signal your control system accepts. We will confirm the model — or tell you which one fits better — before you commit to an order.

Same family

Other pressure instruments

View the family →