Pressure Transmitters & Controllers
PDD2088 Differential Pressure Transmitter
Bidirectional, 2088 housing

PDD2088 technical data
Measurement
- Range
- −100 kPa to +200 kPa (bi-directional)
- Accuracy class
- 0.2 or 0.5
- Non-linearity
- 0.2
- Hysteresis
- ≤ 0.01 % of span
- Long-term stability
- 0.15 % FS/year
- Overload capability
- 2–3× span
- Temperature effect
- 0.15 %/K
Electrical
- Supply voltage
- DC 24 V (12–36 V)
- Output
- Two-wire 4–20 mA; three-wire 1–5 V
- Load impedance
- 750 Ω
- Insulation resistance
- ≥ 100 MΩ at 100 V DC
Mechanical
- Medium
- Gases compatible with 316L
- Housing material
- Stainless steel
- Process connection
- G1/2″, M20×1.5 or to order
- Ambient temperature
- −30 to +70 °C
- Medium temperature
- −30 to +80 °C
- Storage temperature
- −40 to +85 °C
- Ingress protection
- IP65
Values are for the standard configuration. Ranges, threads, probe lengths and output types outside this table are available on request — the datasheet revision for a custom build is issued with the quotation.
Request the PDF datasheet →Pressure Transmitters & Controllers
PDD2088Differential Pressure Transmitter
Bidirectional, 2088 housing
Bidirectional differential pressure transmitter spanning −100 kPa to 200 kPa, in the standard 2088 housing with a liquid-crystal head. Two-wire 4–20 mA or three-wire 1–5 V, 0.2 accuracy class, stainless body, IP65.
Engineering reply · Evaluation samples available · Custom ranges built to order
- Bidirectional −100 kPa to +200 kPa
- Standard 2088 housing — existing brackets fit
- Two-wire 4–20 mA or three-wire 1–5 V
- 0.2 accuracy class
- G1/2 or M20×1.5, custom to order
How it works
The PDD2088 covers the low-pressure end where most differential measurements actually live: draught, filter loading, cleanroom and duct pressure, and low-range level. It reads both directions, from −100 kPa to +200 kPa, so gauge and vacuum duties share one model. Output is two-wire 4–20 mA or three-wire 1–5 V, and the 2088 housing is the industry-standard shape, which means existing brackets, manifolds and spare parts fit. Process connection is G1/2 or M20×1.5, with custom threads available.
Typical applications
- Filter and bag-house differential pressure
- Duct and cleanroom pressure
- Low-range tank and reservoir level
- Airflow measurement in ventilation
Not certain PDD2088 is the right unit?
Send the medium, range, process connection and the signal your control system accepts. We will confirm the model — or tell you which one fits better — before you commit to an order.
Same family
Other pressure instruments

Differential Pressure Transmitter
0.2 class, 40:1 turndown
Differential pressure transmitter covering 0–0.2 kPa to 40 MPa with a 40:1 turndown and 0.2 accuracy class. Two-wire 4–20 mA, 750 Ω load, stainless housing, IP65. Built on a δ-cell capacitive sensor with a 0.10 mm measuring diaphragm.
View specifications
Differential Pressure Transmitter
Compact stainless body
Compact differential pressure transmitter, −100 kPa to 200 kPa, in a small stainless body for tight installation space. Two-wire 4–20 mA or three-wire 1–5 V, 0.2 accuracy class, G1/2 or M20×1.5, IP65.
View specifications
Pressure Transmitter Controller
4 relays
Pressure transmitter with a 24-bit A/D, LED display, four relay outputs and selectable analogue output. −0.1 to 60 MPa, 0.2 accuracy class, diffusion-silicon, ceramic piezoresistive or ceramic capacitive sensor, stainless and aluminium housing.
View specifications
Pressure Transmitter Controller
5 relays, 150 mm case
Five relay outputs in a Φ150 mm gauge case, with dual 24 V DC / 220 V AC supply so it replaces a mechanical gauge in situ. −0.1 to 60 MPa, 0.2 accuracy class, high-brightness LED display, selectable analogue output.
View specifications